10-20KVA UPS DOUBLE...

10-20KVA UPS DOUBLE CONVERSION TRANSFORMER-LESS

Ultra-Power series UPS is a three-phase in and three-phase out high-frequency UPS with medium and large power capacity. benefits from the high-efficiency transformer-less double conversion technology. Ultra-Power series can achieve 94.5% efficiency.


Overview Specifications Ordering Information

Overview

Ultra-Power series UPS is a three-phase in and three-phase out high-frequency UPS with medium and large power capacity. benefits from the high-efficiency transformer-less double conversion technology. Ultra-Power series can achieve 94.5% efficiency.

Specifications

General Features

 

  • High power density design
  • N+X parallel redundancy, support maximum 4 units in parallel
  • Online double conversion with DSP control
  • Input current harmonic:<3%
  • Wide input voltage range:208~478Vac
  • Wide input frequency range:40~70Hz
  • Optimization battery group, the quantity of battery: 16/18/20pcs
  • Maximum charging current up to 18A (Selectable)
  • Generator compatible
  • ECO mode operation for energy saving
  • Intelligent fan speed regulation
  • Self-testing when UPS startup
  • 50/60Hz frequency converter mode

Specification

Model CN93310U
CN93315U 
CN93320U 

Capacity

kVA

10

15 20

Watts

9kW

13.5kW 18kW

Input

Normal Voltage 380/400/415Vac (3Ph+N+PE)
Operating voltage range 305~478Vac(Full load); 208~478Vac(50% load)
Harmonic distortion(THDi)  <3%(linear load)
Operating frequency range 40~70Hz (50/60Hz Auto-Sensing)
Power factor ≥0.99
Bypass voltage range

220Vac Max.Voltage:+25% (optional +10%,+15%,+20%) 230Vac Max.Voltage:+20%(optional +10%,+15%) 240Vac Max.Voltage:+15%(optional +10%) Min.Voltage:-45%(optional -20%,-30%)

Bypass Frequency range Frequency synchronize tracing range:±10%
Generator input Support

Output

Rated voltage 380/400/415Vac (3Ph+N+PE)
Power factor 0.9
Voltage regulation ±1%
Frequency    Line mode ±1%/±2%/±4%/±5%/±10% of the rated frequency (Optional)
                              Frequency   Bat. mode 50/60(±0.1)Hz
Crest factor 3:1
Harmonic distortion (THDv) ≤2% with linear load, ≤5% with non-linear load
Efficiency 94.5%
Output Waveform Pure SineWave

Battery

Battery voltage ±96/108/120Vdc(16/18/20pcs)
Charging current (Charging current can be set according to the battery capacity installed)  14A

   

16A                               

 

   

18A                               

 

System Features

Transfer time Mains to battery:0ms; Mains to bypass:0ms
Overload  Line mode ≤110%: Overload 60min, ≤150%: Overload 1min, >150% turn to bypass mode immediately
Overload  Bypass mode ≤110%,last 10min; ≤125%,last 1min; ≤150%,last 5s; >150% turn to bypass Immediately
Backfeed Protection  Support
Alarm Overload, utility abnormal, UPS fault, battery low, etc
Protection Short circuit, overload, over-temperature, battery low, fan fault alarm
Communication USB, RS232, RS485, Parallel port,dry contact, Intelligent slot, LBS, SNMP card (optional), Relay card (optional) 

Environment

Operating temperature 0~40°C
Storage temperature -25~55°C
Humidity range 0~95% (Non-condensing)
Altitude <1500m
Noise level <55dB   <58db

Physical

Dimension WxDxH(mm) 250x580x655
Net Weight (kg) 35 39 40

Standards

Safety IEC/EN62040-1,IEC/EN62477-1
EMC IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8

 

Ordering Information

Part Number Description
CN93310U 10kVA Double Conversion Transformer-less UPS
 CN93315U 15kVA Double Conversion Transformer-less UPS
CN93320U 20kVA Double Conversion Transformer-less UPS