Ultra Power Series is a transformer-based UPS of Cellnor, both input and output are 3 phases. The output power factor is 0.9. These ups can work in parallel and expand its power capacity. This series UPS is highly reliable and have good impact resistance, it can supply safe and reliable protection for the load. 


Overview Specifications Ordering Information

Overview

Ultra Power Series is a transformer-based UPS of Cellnor, both input and output are 3 phases. The output power factor is 0.9. These ups can work in parallel and expand its power capacity. This series UPS is highly reliable and have good impact resistance, it can supply safe and reliable protection for the load. 

Specifications

GENERAL FEATURES

 

 

 

  • Online Double Conversion
  • Full DSP Control
  • High Power Factor
  • Wide input adptability
  • Optimized battery management
  • N+X parallel redundancy
  • Strong overload capability
  • Multi-protection
  • Generator mode
  • EPO function 

 

Specification

Model CN43310TU 
CN43310TU 
CN43310TU 

Capacity

kVA

10kVA

20kVA 30kVA

Watts

9kW

18kW 18kW

Input

Normal Voltage 380/400/415Vac (3Ph+N+PE) (-25% +20%)
Harmonic distortion(THDi)  <3%(100% linear load) 
Operating frequency range 50/60Hz (±5Hz) 
Power factor 0.98 (with filter)
Bypass voltage range

Upper limit:+20%(+10%,+15%,+20% adjustable)

Lower limit:-40%(-10%,-20%,-30%,-40% adjustable)

Bypass Frequency range ±10%(±2.5%,±5%,±10%,±20% adjustable)

Output

Rated voltage 380/400/415Vac (3Ph+N+PE)
Power factor 0.9
Voltage regulation ±1%
Frequency    50/60(±0.1)Hz
Crest factor 3:1
Harmonic distortion (THDv) ≤2% with linear load
Efficiency >88%                                                                           >89%
Output Waveform Pure Sine Wave

Battery

Battery voltage 384Vdc (30/32pcs)

System Features

Transfer time Mains to battery:0ms; Mains to bypass:0ms
Overload   ≤110%: Overload 60min, ≤150%: Overload 1min, >150% turn to bypass mode immediately
LED Display Input, Inverter, Bypass, Battery, Output, Status 
LCD Display  I/O voltage, frequency, power, power factor, battery voltage, current, battery status, load percentage, UPS status, history record, settings
Communication  USB, RS232, RS485, Parallel port, dry contact, Intelligent slot, LBS, SNMP card (optional), Relay card (optional)

Environment

Operating temperature 0~40°C
Storage temperature -25~55°C
Humidity range 0~95% (Non-condensing)
Altitude <1500m
Noise level <70dB

Physical

Dimension WxDxH(mm) 570x800x1195
Net Weight (kg) 217 273 316

Standards

Safety IEC/EN62040-1,IEC/EN60950-1
EMC

IEC/EN 62040-2;IEC 61000-2-2;IEC 61000-4-2;IEC 61000-4-3;IEC 61000-4-4 IEC 61000-4-5;IEC 61000-4-6;IEC 61000-4-8;IEC 61000-4-11 2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8

Performance IEC62040-3

 

                                                                      

Ordering Information

Part Number Description
CN43310TU 10kVA Double Conversion Transformer-Based UPS 
CN43320TU 20kVA Double Conversion Transformer-Based UPS