2C 18 AWG Power Limi...

2C 18 AWG Power Limited Fire Protective Unshielded Signal Cable FPLR

75-810218E

The unshielded power limited fire protective cable from NORDEN is suitable to be used for fire limited fire protective, control and instrumentation purposes. The cable is constructed with FPL-PVC insulation and FPLR & CMR rated outer jacket.


Overview Specifications Ordering Information

Overview

The unshielded power limited fire protective cable from NORDEN is suitable to be used for fire limited fire protective, control and instrumentation purposes. The cable is constructed with FPL-PVC insulation and FPLR & CMR rated outer jacket.

Specifications

CABLE CONSTRUCTION

Conductor

Solid Bare Copper

Outer Jacket

PVC (FPLR & CMR)

Insulation

PVC (FPL)

Jacket Colour

Red

Insulation Colour

2 Core: Red/Black

Standard Packing Mode

305 mtr / Plywood Reel

PHYSICAL CHARACTERISTICS

Characteristic Value

No. of Conductor

2

Conductor Size

18 AWG

Jacket Thickness

0.45 mm

Jacket Diameter

5.8 mm

Min. Bending Radius (Install)

8XD

Operating Temperature

-20°C  to  +75°C

ELECTRICAL CHARACTERISTICS

Characteristic Value Unit

Nom Conductor DCR @ 20°C

?/km

20.7

Nom. Inductance

?H/m

0.55

Nom. Capacitance Cond. to Cond.

pF/m

72.3

Max. Recommended Current @ 25°C

Amps

8.2

Max. Operating Voltage

V rms

300

MECHANICAL CHARACTERISTICS

Characteristic Value

Test Material

FPLR

Before Tensile Strength (Mpa)

?13.8

Aging Elongation (%)

?100

After Tensile Strength (Mpa)

?85

Aging Elongation (% of unaged)

?100

Cold Bend (-20±°C x 4 hrs)

No Crack

Ordering Information

Part Number Description Weight (Kg)

75-810218E

2 CORE 18 AWG Power Limited Fire Protective Unshielded Signal Cable FPLR, 305m

11.7