Voice Evacuation System Host
Overview Specifications Ordering Information
SPECIFICATIONS | ||||
Model |
NVS-50010508EV |
|||
Rated Output Power |
≥500W(100V) |
|||
Input sensitivity |
Emergency mic |
5mV 600Ω |
||
Line |
1000mV 10kΩ |
|||
Harmonic Distortion |
Emergency Mic |
<1% 1kHz |
||
Line |
<1% 1kHz |
|||
Frequency response |
Emergency Mic |
80Hz-15kHz(±3dB) |
||
Line |
50Hz-18kHz(±3dB) |
|||
Signal to noise ratio |
Emergency Mic |
>75dB(A weighting) |
||
Line |
>80dB(A weighting) |
|||
Line Output |
Output voltage |
1000mV |
||
Frequency range |
80Hz-15kHz(±3dB) |
|||
Harmonic Distortion |
<1% 1kHz |
|||
System |
System fault relay output |
Short circuit, no voltage |
||
Emergency mode relay output |
Short circuit, no voltage |
|||
Fire reset input |
Short circuit, t≥0.5S, no voltage |
|||
8 channel dry contact output |
Short circuit, no voltage |
|||
8 dry contact |
|
Short Circuit |
Short circuit, no voltage |
|
Level Mode |
3.3V~24V |
|||
Voice Message |
Data Format |
WAV |
||
Storage Form |
SD card |
|||
Storage Time |
>10 years |
|||
Working Power |
AC |
AC 220V/50Hz |
||
|
DC |
DC 24V/30A |
||
Package size (L*W*H) |
550×510×215mm |
|||
Machine size (L*W*H) |
483×420×132mm |
|||
G.W |
14Kg |
|||
N.W |
12.05Kg |
Part Number | Description | Standard Quantity |
NVS-50010508EV |
500W 8 Zones Voice Evacuation System Host |
1 No. |