Norden Category 6A F/FTP cables exceed Category 6A/Class EA specification. It is tested to 500MHz frequency range and designed to support 10 Gigabyte applications to full 100m. Data integrity is one of the most essential network requirements for many corporations, especially those located in environments that are prone to noise...
Overview Specifications Ordering Information
COMPLIANCEIEEE 802.af,IEEE 802.3at for PoE applications |
Product Sequence | Premium |
Product Type | Twisted Pair Cable |
Conductor Material |
Bare Copper |
Conductor Size |
0.57 mm, 23 AWG |
Conductor Construction |
Solid |
Insulation Material |
SFS PE |
Insulation O.D. |
1.35 mm nom. |
Conductor Unit Identification |
Solid/Stripe |
Colour Code |
Per TIA/EIA 568-B |
In. Shield Material |
Aluminium/Polyester Foil |
In. Shield Design |
100 % Coverage |
Overall Shield Design |
100 % Coverage |
Overall Foil Shield |
Yes |
Overall Shield Material |
Aluminium/Polyester Foil |
Overall Drain-Wire Material |
Tinned Copper |
Overall Drain-Wire Size |
0.41 mm |
Overall Drain-Wire Construction |
Solid |
Total number of Wires |
8 |
Outer Jacket |
LSZH Low Smoke Zero Halogen or PVC |
Outer Jacket Thickness & Ex. Diameter |
0.55±0.05 mm, 7.6±0.5 mm |
Rip Cord |
Yes |
Outer Jacket Colour |
Per Requirement |
Marking |
Per Requirement |
Frequency Range |
1 - 500 MHz |
Impedance |
100 Ω |
Coupling Attenuation |
85 dB min @ 30-100 MHz 85-20Log (f/100) @100-500 MHz |
DC Resistance |
78 Ω/km nom. |
Max. Resistance Unbalance |
2 % |
Capacitance Unbalance |
1.2 pF/m max. |
Velocity of Propagation |
80 % nom. |
Propagation Delay Skew |
25 ns/100m max. |
Dielectric Strength |
1.5 KV/minute |
Dielectric Strength to Shield |
1.5 KV/minute |
Min. Insulation Resistance |
5 GΩ•km |
Transfer Impedance |
1000 mΩ/m max. @ 100 MHz. |
Max. Tensile Strength - Short Term |
130 N |
Min. Bend Radius |
50 mm |
Operating Temperature Range |
-20 °C +60 °C |
Cat. 6A Screened-pair Horizontal Cables*
Freq. MHz |
Attenuation dB/100m @ 20°C |
NEXT dB |
PSNEXT dB |
RL dB |
ACR dB |
ELFEXT dB |
PS.ACRF dB |
1 |
1.7 |
87.2 |
84.0 |
23.0 |
85.5 |
84.0 |
81.0 |
4 |
3.4 |
84.0 |
81.0 |
23.0 |
80.6 |
81.0 |
78.0 |
10 |
5.4 |
80.2 |
77.2 |
25.0 |
74.8 |
76.0 |
73.0 |
20 |
7.6 |
77.0 |
73.8 |
25.0 |
69.4 |
70.0 |
67.0 |
31.25 |
9.7 |
75.6 |
72.6 |
23.8 |
65.9 |
65.0 |
63.0 |
100 |
18.0 |
72.0 |
69.0 |
21.1 |
54.0 |
55.0 |
52.8 |
150 |
23.6 |
69.0 |
66.0 |
18.8 |
45.4 |
53.5 |
51.5 |
200 |
27.4 |
66.9 |
63.9 |
18.0 |
43.3 |
49.0 |
46.0 |
250 |
31.0 |
64.5 |
61.5 |
17.3 |
33.5 |
44.0 |
41.0 |
300 |
34.2 |
62.0 |
58.9 |
16.8 |
24.8 |
39.6 |
36.6 |
400 |
40.0 |
59.0 |
56.1 |
16.8 |
19.0 |
37.0 |
34.0 |
500 |
42.2 |
57.0 |
54.2 |
16.8 |
14.8 |
35.0 |
33.0 |
*Supplied cables meets Cat. 6a min. transmission requirements as per IEC 61156-5 Ed. 2
Part Number | Description | Standard Length |
114-10001404X | Category 6a F/FTP Pair Cable PVC | 305 mtr |
114-10002404X | Category 6a F/FTP Pair Cable LSZH | 305 mtr |
X: BK(Black), BL(Blue), GN(Green), GY(Gray), RD(Red), WH(White), YL(Yellow)