The UL listed FPLR shielded fire alarm E-series cable from Norden is suitable to be use in a vertical runs in signaling & fire alarm system. It works in high temperature levels. This cable is constructed with FR-PVC insulation and outer jacket with aluminum foil shielding that meets UL 1666...
Overview Specifications Ordering Information
Properties | Value | |
14AWG | 16AWG | |
Max. Conductor Resistant @ 20ºC |
8.45 Ω/km |
13.5 Ω/km |
Min. Insulation Resistant @ 15.6°C |
100Ω/kft |
|
Operating Voltage |
300/500 V |
|
Breakdown Test |
2500 V |
|
Temperature Range |
-35°C to +105°C |
No. of Cores x Conductor Size |
Conductor diameter mm (±0.005) | Insulation diameter mm (±0.1) | Jacket Thicknes mm (±0.01) | Jacket diameter, mm (±0.3) |
2C x 14 AWG |
1.63 |
2.7 | 0.58 | 6.8 |
2C x 16 AWG |
1.29 |
2.2 | 0.58 | 5.8 |
Part Number | Description |
5E-1502XY |
2Core x 16 AWG FPLR Shielded Fire Alarm Cable E-Series |
5E-2502XY |
2Core x 14 AWG FPLR Shielded Fire Alarm Cable E-Series |