Online Transformerle...

Online Transformerless 10kVA RM UPS

MAXPOWER PRO is a small to 10kVA Online Double Conversion Rack Mount UPS of CellNor. This UPS has a high output power factor at 1.0PF and a wide input voltage range 208~478Vac. The CN5310MP-RM model support economic (ECO) operation mode.


Overview Specifications Ordering Information

Overview

MAXPOWER PRO is a small to 10kVA Online Double Conversion Rack Mount UPS of CellNor. This UPS has a high output power factor at 1.0PF and a wide input voltage range 208~478Vac. The CN5310MP-RM model support economic (ECO) operation mode.

Specifications

 GENERAL FEATURES

  • LCD support Rack/Tower convertible design
  • N+X parallel redundancy, support maximum  4 units in parallel 
  • Online double conversion with full digital control
  • Wide input frequency range 40~70Hz 
  • Wide input voltage range:208~478Vac
  • Input current harmonic:<3%
  • Maximum Charging current up to 20A(Settable) 
  • Dual Input Sources
  • ECO mode operation for energy saving
  • Support 3/3 and 3/1 and 1/1 operation 
  • Generator compatible
  • Cold Start
  • Self-testing when UPS start-up
  • 50/60Hz Frequency converter mode
  •  Intelligent fan speed regulation 
  • The quantity of battery:30-50pcs is settable

 

 

 

 

 

Model CN5310MP-RM

Capacity

kVA

10kVA

Watts

10000

Input

Normal Voltage

380/400/415Vac (3Ph+N+PE) 220/230/240Vac (L+N+PE)

Operating Voltage Range

208~478Vac

Operating Frequency Range

40~70Hz (50/60Hz Auto-Sensing)

Power Factor

≥0.99

Bypass voltage range

Max.voltage:220V:+25% (Optional+10%,+15%,+20%) 240V:+15% (Optional+10%) Min.voltage:-45% (Optional-20%,-30%), 230V:+20% (Optional+10%,+15%)

ECO range

Same as the bypass

Generator input

Support

Output

Rated voltage

380/400/415Vac (3Ph+N+PE) 220/230/240Vac (L+N+PE)

Power factor

1.0

Voltage Regulation

±1%

Frequency

Line mode

±1%/±2%/±4%/±5%/±10% of the rated frequency (Optional)

Bat. mode

50/60(±0.1)Hz

Crest Factor

3:1

Harmonic Distortion (THDv)

≤2% with linear load, ≤5% with non-linear load

Efficiency

94.5%

Output Waveform Pure Sine Wave

Battery

Battery voltage

30/32/34/36/38/40/42/44/46/48/50pcs with Neutral

Charging current

18A Max.(charge current can be set according to battery capacity installed)

System
Features

Transfer time

Mains to battery:0ms; Mains to bypass:0ms

Overload

Line mode

Load≤110%: last 60min, ≤125%: last 10min, ≤150%: last 1min, >150% turn to bypass mode immediately

Bypass mode

Breaker ( Load < 125%, long-term operation)

Short circuit

Hold whole system

Overheat

Line mode: Turn to bypass; Backup mode: shut down UPS immediately

Battery low

Alarm and switch off

Self-diagnostics

Upon power on and software control

Battery

Advanced battery management

Audible & Visual alarms

Line failure, Battery under voltage, Overload, System fault

LED & LCD display

Line mode, Bat. mode, Eco mode, Bypass mode, Battery under voltage, Overload & UPS Fault 

LCD display

Input voltage, Input frequency, Output voltage, Output frequency, Load percentage, Battery voltage, Inner temperature & Remaining battery backup time

Communication interface

RS232, RS485, Parallel, Intelligent Slot(SNMP card/ Relaycard (Optional)),BMS (Optional),EPO port Output port, MAINTAIN-AUXSWS port

Environment

Operating temperature

0~40°C 

Storage temperature

-25~55°C

Humidity range

0~95% (Non-condensing)

Altitude

<1500m

Noise level

<55dB 

Standards

Safety

IEC/EN62040-1,IEC/EN62477-1

EMC

IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8

Physical

Dimension WxDxH(mm)

443 x 580 x 131            

Net Weight (kg)

29

 EXTERNAL BATTERY PACK

MODEL CNBN15240CR
BATTERY SYSTEM  

Battery type

VRLA (Lead acid maintenance free battery)

Typical battery recharging time 

6~8 hours (to 90% of full capacity) 

Typical battery life 3~5 years, depend on discharging cycle and ambient temperature
System voltage  ±240Vdc
Battery quantity 1*±20 PCS
Capacity 7Ah/9Ah (12V)
Backup time @ 50% load 10 Minutes
Backup time @ 100% load  5 Minutes
PHYSICAL  
Dimension W x D x H (mm)  443x861.5x175
Net weight (kg) 114/123
ENVIRONMENT  
Safety  CE
Operating environment 0°C~40°C
Relative humidity  0~95% (Non condensing) 
Noise level  <40dB at 1 Meter
             

Ordering Information

Part Number Description

CN5310MP-RM

10kVA Online Double Conversion UPS Rack Mount

CNBN10240CR

240Vdc Battery Pack