Online Transformerle...

Online Transformerless 15kVA UPS

Maxpower Series is a small to medium power transformer-less UPS of CellNor. This is an online double conversion UPS with power factor of 0.9. The CN7315MP model supports ECO operation mode


Overview Specifications Ordering Information

Overview

Maxpower Series is a small to medium power transformer-less UPS of CellNor. This is an online double conversion UPS with power factor of 0.9. The CN7315MP model supports ECO operation mode

Specifications

GENERAL FEATURES

  • Online double conversion with DSP control
  • Wide input range:208~478Vac
  • Wide input frequency range:40~70Hz
  • Support parallel function(Optional)
  • Optimization battery group, the quantity of battery:16/18/20pcs
  • Support 3/1 and 1/1 operation
  • Maximum charging current up to 16A(Settable)
  • ECO mode operation for energy saving
  • Cold start
  • Intelligent fan speed regulation
  • Self-testing when UPS start-up

 

 

Model CN7315MP

Capacity

VA

15000

Watts

13500

Input

Normal Voltage 380/400/415Vac; (3Ph+N+PE), 220/230/240Vac (L+N+PE)

Operating Voltage Range

208~478Vac; 120~276Vac

Operating Frequency Range

40~70Hz (50/60Hz Auto-Sensing)

Power Factor

≥0.99 

Bypass voltage range

Max.voltage: 220V: +25%(optional +10%,+15%,+20% )

230V: +20% (optional +10%,+15%),

240V: +15% (optional +10%)

Min.voltage: -45% (optional -20%,-30%)

Bypass Freq Range Frequency protection range:±10%Frequency protection range:±10%
Generator Input Support

Output

Rated voltage 220/230/240Vac 

Power Factor

0.9

Voltage Regulation

±1%

Freq. Line mode

±1%/±2%/±4%/±5%/±10% of the rated frequency(optional)

Freq. Bat. mode

50Hz / 60Hz (±0.1)Hz

Crest Factor

3:1

Harmonic Distortion (THDv)

≤2% with linear load, ≤5% with non-linear load

Efficiency

>93.5%

Battery

Battery Voltage

192/216/240Vdc

±96/108/120Vdc (optional)

12V/7Ah/9Ah

Typical recharging Time

6~8 hours (to 90% of full capacity)

Charging current

2.7A standard unit) ; Max.current 16A(Long run unit)

System features

Transfer time Mains to battery:0ms; Mains to bypass:0ms

Overload

Line mode: Load≤110%: last 60min, ≤125%: last 10min, ≤150%: last 1min, >150% turn to bypass mode immediately

Bypass mode: 63A(Breaker)

Short circuit

Hold whole system

Overheat

Line mode: Turn to bypass; Backup mode: shut down UPS immediately

Battery low Alarm and switch off
Self-diagnostics Upon power on and software control
Battery Advanced battery management
Audible & Visual alarms Line failure, Battery under voltage, Overload, System fault
LED and LCD Display Line mode, Bat. mode, Eco mode, Bypass mode, Battery under voltage, Overload & UPS Fault
LCD Display Input voltage, Input frequency, Output voltage, Output frequency, Load percentage, Battery voltage, Inner temperature & Remaining battery backup time
Communication interface RS232, USB,SNMP card(optional), Parallel card(optional), Relay card (optional)

Environment

Operating temperature

0~40°C

Storage temperature

-25~55°C

Humidity range

0~95% (Non-condensing)

Altitude

<1500m

Noise Level <55dB at 1 Meter

Physical

Dimension E: 220 x 531 x 450 ; I:250 x 900 x 868

Weight

24/167

 

STANDARDS  

Safety

IEC/EN62040-1, IEC/EN60950-1
EMC IEC/EN62040-2, IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8

                                                                     

Ordering Information

Part Number Description

CN7315MP

15kVA Medium Power Transformerless UPS