MAXPOWER PRO is a small to 20kVA Online Double Conversion Rack Mount UPS of CellNor. This UPS has a high output power factor at 1.0PF and a wide input voltage range 208~478Vac. The CN5320MP-RM model support economic (ECO) operation mode.
Overview Specifications Ordering Information
GENERAL FEATURES
Model | CN5320MP-RM | ||
Capacity |
kVA |
20kVA |
|
Watts |
20000 |
||
Input |
Normal Voltage |
380/400/415Vac (3Ph+N+PE) 220/230/240Vac (L+N+PE) | |
Operating Voltage Range |
208~478Vac |
||
Operating Frequency Range |
40~70Hz (50/60Hz Auto-Sensing) |
||
Power Factor |
≥0.99 |
||
Bypass voltage range |
Max.voltage:220V:+25% (Optional+10%,+15%,+20%) 240V:+15% (Optional+10%) Min.voltage:-45% (Optional-20%,-30%), 230V:+20% (Optional+10%,+15%) |
||
ECO range |
Same as the bypass |
||
Generator input |
Support |
||
Output |
Rated voltage |
380/400/415Vac (3Ph+N+PE) 220/230/240Vac (L+N+PE) | |
Power factor |
1.0 |
||
Voltage Regulation |
±1% |
||
Frequency |
Line mode |
±1%/±2%/±4%/±5%/±10% of the rated frequency (Optional) | |
Bat. mode |
50/60(±0.1)Hz |
||
Crest Factor |
3:1 |
||
Harmonic Distortion (THDv) |
≤2% with linear load, ≤5% with non-linear load |
||
Efficiency |
95% |
||
Output Waveform | Pure Sine Wave | ||
Battery |
Battery Number |
30/32/34/36/38/40/42/44/46/48/50pcs with Neutral | |
Charging current |
20A Max.(charge current can be set according to battery capacity installed) |
||
System |
Transfer time |
Mains to battery:0ms; Mains to bypass:0ms | |
Overload |
Line mode |
Load≤110%: last 60min, ≤125%: last 10min, ≤150%: last 1min, >150% turn to bypass mode immediately | |
Bypass mode |
40A(Breaker) |
||
Short circuit |
Hold whole system |
||
Overheat |
Line mode: Turn to bypass; Backup mode: shut down UPS immediately |
||
Battery low |
Alarm and switch off |
||
Self-diagnostics |
Upon power on and software control |
||
Battery |
Advanced battery management |
||
Audible & Visual alarms |
Line failure, Battery under voltage, Overload, System fault |
||
LED & LCD display |
Line mode, Bat. mode, Eco mode, Bypass mode, Battery under voltage, Overload & UPS Fault |
||
LCD display |
Input voltage, Input frequency, Output voltage, Output frequency, Load percentage, Battery voltage, Inner temperature & Remaining battery backup time |
||
Communication interface |
RS232, RS485, Parallel, Intelligent Slot(SNMP card/ Relaycard (Optional)),BMS (Optional),EPO port Output port, MAINTAIN-AUXSWS port |
||
Environment |
Operating temperature |
0~40°C | |
Storage temperature |
-25~55°C |
||
Humidity range |
0~95% (Non-condensing) |
||
Altitude |
<1500m |
||
Noise level |
<58dB |
||
Standards |
Safety |
IEC/EN62040-1,IEC/EN62477-1 | |
EMC |
IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 |
||
Physical |
Dimension WxDxH(mm) |
443 x 580 x 131 | |
Net Weight (kg) |
32 |
MODEL | CNBN20240CR | ||
BATTERY SYSTEM | |||
Battery type |
VRLA (Lead acid maintenance free battery) |
||
Typical battery recharging time |
6~8 hours (to 90% of full capacity) |
||
Typical battery life | 3~5 years, depend on discharging cycle and ambient temperature | ||
System voltage | ±240Vdc | ||
Battery quantity | 1*±20 PCS | ||
Capacity | 7Ah/9Ah (12V) | ||
Backup time @ 50% load | 5 Minutes | ||
Backup time @ 100% load | 2 Minutes | ||
PHYSICAL | |||
Dimension W x D x H (mm) | 443x861.5x175 | ||
Net weight (kg) | 114/123 | ||
ENVIRONMENT | |||
Safety | CE | ||
Operating environment | 0°C~40°C | ||
Relative humidity | 0~95% (Non condensing) | ||
Noise level | <40dB at 1 Meter |
Part Number | Description | ||
CN5320MP-RM |
20kVA Online Double Conversion UPS Rack Mount |
||
CNBN20240CR |
240Vdc Battery Pack |