Maxpower Series is a small to medium power transformer-less UPS of CellNor. This is an online double conversion UPS with power factor of 0.9. The CN7320MP model supports ECO operation mode.
Overview Specifications Ordering Information
GENERAL FEATURES
|
|
Model | CN7320MP | |
Capacity |
VA |
20000 |
Watts |
18000 |
|
Input |
Normal Voltage | 380/400/415Vac; (3Ph+N+PE), 220/230/240Vac (L+N+PE) |
Operating Voltage Range |
208~478Vac, 120~276Vac |
|
Operating Frequency Range |
40~70Hz (50/60Hz Auto-Sensing) |
|
Power Factor |
≥0.99 |
|
Bypass voltage range |
Max.voltage: 220V: +25%(optional +10%,+15%,+20% ) 230V: +20% (optional +10%,+15%), 240V: +15% (optional +10%) Min.voltage: -45% (optional -20%,-30%) |
|
Bypass Freq Range | Frequency protection range:±10% | |
Generator Input | Support | |
Output |
Rated voltage | 220/230/240Vac |
Power Factor |
0.9 |
|
Voltage Regulation |
±1% |
|
Freq. Line mode |
±1%/±2%/±4%/±5%/±10% of the rated frequency(optional) | |
Freq. Bat. mode |
50Hz / 60Hz (±0.1)Hz |
|
Crest Factor |
3:1 |
|
Harmonic Distortion (THDv) |
≤2% with linear load, ≤5% with non-linear load |
|
Efficiency |
>94% |
|
Battery |
Battery Voltage |
192/216/240Vdc |
±96/108/120Vdc (optional) |
12V/7Ah/9Ah |
|
Typical recharging Time |
6~8 hours (to 90% of full capacity) |
|
Charging current |
2.7A standard unit) ; Max.current 18A(Long run unit) |
|
System features |
Transfer time | Mains to battery:0ms; Mains to bypass:0ms |
Overload |
Line mode: Load≤110%: last 60min, ≤125%: last 10min, ≤150%: last 1min, >150% turn to bypass mode immediately Bypass mode: 125A(Breaker) |
|
Short circuit |
Hold whole system |
|
Overheat |
Line mode: Turn to bypass; Backup mode: shut down UPS immediately |
|
Battery low | Alarm and switch off | |
Self-diagnostics | Upon power on and software control | |
Battery | Advanced battery management | |
Audible & Visual alarms | Line failure, Battery under voltage, Overload, System fault | |
LED and LCD Display | Line mode, Bat. mode, Eco mode, Bypass mode, Battery under voltage, Overload & UPS Fault | |
LCD Display | Input voltage, Input frequency, Output voltage, Output frequency, Load percentage, Battery voltage, Inner temperature & Remaining battery backup time | |
Communication interface | RS232, USB,SNMP card(optional), Parallel card(optional), Relay card (optional) | |
Environment |
Operating temperature |
0~40°C |
Storage temperature |
-25~55°C |
|
Humidity range |
0~95% (Non-condensing) |
|
Altitude |
<1500m |
|
Noise Level | <58dB at 1 Meter | |
Physical |
Dimension | E: 220 x 531 x 450 ; I:250 x 900 x 868 |
Weight |
28/171 |
Specifications are subject to change without prior notice
STANDARDS | |
Safety |
IEC/EN62040-1, IEC/EN60950-1 |
EMC | IEC/EN62040-2, IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8 |
Part Number | Description | ||
CN7320MP |
20kVA Medium Power Transformerless UPS |