Maxpower RM Series is a small to medium power transformer-less UPS of CellNor. This is an Online double conversion UPS with PFC technology and Full digital control (DSP). It has an Output power factor of 0.9.The CN7010MP-RM model support economic (ECO) operation mode
Overview Specifications Ordering Information
GENERAL FEATURES
Model | CN7010MP-RM | ||
Capacity |
VA |
10000 |
|
Watts |
9000 |
||
Input |
Normal Voltage |
220/230/240Vac(L+N+PE) | |
Operating Voltage Range |
110~286Vac |
||
Operating Frequency Range |
40~70Hz (50/60Hz Auto-Sensing) |
||
Power Factor |
≥0.99 |
||
Bypass voltage range |
Max. voltage: 220V: +25%(optional +10%,+15%,+20% ) 230V: +20% (optional +10%, +15%) 240V: +15% (optional +10%) Min. voltage: -45% (optional -20%, -30%) |
||
Bypass Freq Range | Frequency protection range:±10% | ||
ECO range | Same as the bypass | ||
Harmonic distortion (THDi) | ≤5%(100% linear load) | ||
Generator Input | Support | ||
Output |
Output Voltage |
220/230/240Vac | |
Power Factor |
0.9 |
||
Voltage Regulation |
±1% |
||
Frequency Line mode |
±1%/±2%/±4%/±5%/±10% of the rated frequency(optional |
||
Frequency Bat mode |
50/60(±0.1)Hz |
||
Crest factor |
3:1 |
||
Harmonic Distortion (THDv) |
≤2% with linear load, ≤5% with non-linear load |
||
Efficiency |
>94% |
||
Battery |
Internal |
Battery Voltage |
192/216/240Vdc (Adjustable) |
Backup time |
Long run unit depends on the capacity of external batteries Estimated remaining time displayed on the LCD |
||
Typical Recharging Time |
6~8 hours (to 90% of full capacity |
||
Charging current |
Maximum current 10A; charging current can be set according to battery capacity installed |
||
System Features |
Transfer time |
Mains to battery:0ms; Mains to bypass:0ms | |
Overload Line Mode |
Load≤110%:60min; ≤125%:last 10min; ≤150%:last 1min;>150% turn to bypass mode |
||
Overload Bypass Mode |
63A(Input breaker) |
||
Short circuit |
Hold whole system |
||
Overheat | Line mode: Turn to bypass; Backup mode: shut down UPS immediately | ||
Battery Low | Alarm and switch off | ||
Self-diagnostics | Upon power on and software control | ||
Battery | Advanced battery management | ||
Audible & Visual alarms | Line failure, Battery under voltage, Overload, System fault | ||
LED & LCD display | Line mode, Bat. mode, Eco mode, Bypass mode, Battery under voltage, Overload & UPS Fault | ||
LCD Display | Input voltage, Input frequency, Output voltage, Output frequency, Load percentage, Battery voltage, Inner temperature & Remaining battery backup time | ||
Communication interface | RS232,USB,SNMP card(optional), Relay card (optional) | ||
Environment |
Operating temperature |
0~40°C | |
Storage temperature | -25~55°C | ||
Humidity Range |
0~95% (Non-condensing |
||
Altitude | <1500m | ||
Noise Level | 58dB at 1 Meter | ||
Physical |
Dimension |
440x625x86.5 | |
Weight |
18 |
||
Standards |
Safety |
IEC/EN62040-1,IEC/EN62477-1 | |
EMC |
IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 |
EXTERNAL BATTERY PACK | |
Model | CNBC10120CR |
Battery Type |
VRLA (Lead acid maintenance free battery) |
Typical battery recharging time | 6~8 hours (to 90% of full capacity) |
Typical Battery Life | 3~5 years, depend on discharging cycle and ambient temperature |
System Voltage |
±120Vdc |
Battery Qty | 1*±10 pcs |
Capacity |
7Ah/9Ah (12V) |
Backup time @ 50% load | 7 minutes |
Backup time @ 100% load | 2 minutes |
Dimension | 440 x 680 x 131 |
Net weight(kg) | 58/63 |
Environment safety | CE |
Operating environment | 0°C~40°C |
Relative humidity | 0~95% (Non condensing) |
Noise Level | <40dB at 1 Meter |
Part Number | Description | ||
CN7010MP-RM |
10kVA Medium Power Transformerless UPS Rack Mount |
||
CNBC10120CR |
120 Vdc Battery Pack |