MAXPOWER Series is a small to medium power transformer-less UPS of CellNor. This series has Rack/Tower convertible design and a high output power factor at 0.9PF. It has a Hot-Swappable Battery and support Economic (ECO) Operation Mode. CN7003MPI-RM/CN7003MPE-RM is a true online double conversion UPS with efficiency up to 90%.
Overview Specifications Ordering Information
GENERAL FEATURES
Model | CN7003MPI-RM/CN7003MPE-RM | ||
Capacity |
VA |
3000 |
|
Watts |
2700 |
||
Phase |
Single phase with ground |
||
Input |
Normal Voltage |
208/220/230/240Vac | |
Input Voltage Range |
110~300Vac (176~280Vac @ 100% load) |
||
Frequency Range |
40~70Hz(50/60Hz Auto Sensing |
||
Power Factor |
≥0.99 @Nominal voltage (100% load) |
||
Output |
Output Voltage |
208/220/230/240Vac | |
Power Factor |
0.9 |
||
Voltage Regulation |
±1% |
||
Frequency range (Synchronized range) |
45~55Hz/56~64Hz |
||
Frequency range (Batt.mode) |
50Hz/60Hz±0.1Hz |
||
Current crest ratio |
3:1 |
||
Harmonic Distortion (THDv) |
≤3% THD(Linear load) |
||
≤5% THD(Non-linear load) |
|||
Transfer Time |
AC to DC |
Zero | |
Inverter to Bypass |
4ms(Typical) |
||
Waveform |
Pure Sinewave |
||
Efficiency |
AC Mode |
92% |
|
Battery Mode |
88% |
||
Battery |
Internal |
Battery Type |
12V/9AH |
Numbers |
6 |
||
Backup time |
»5 minutes, remaining time displayed on the LCD |
||
Typical Recharging Time |
4 hours recover to 90% capacity |
||
Charging current(max.) |
1.0A |
||
Charging Voltage |
82.1Vdc ±1% |
||
Battery |
External |
Battery Number |
6 8 |
Battery Voltage |
82.2Vdc ±1% 109.6Vdc ±1% |
||
Charging Current |
6A/12A |
||
Indicators |
LCD |
Load level, Battery level, AC mode, Battery mode, Bypass mode and Fault indicators | |
Alarm |
Battery Mode |
Beeping every 4 seconds | |
Battery Low |
Beeps every second |
||
Overload |
Beeps twice every second |
||
Fault |
Continuously beeping |
||
Physical |
Dimension |
Standard model |
440x600x86.5 |
Long run model |
440x600x86.5 |
||
Weight |
Standard model |
26 |
|
Long run model |
11 |
||
Environment |
Humidity |
20-90% RH @ 0-40°C (Non-condensing) | |
Noise level |
<50dB @ 1 Meter |
||
Management |
Smart RS232/USB |
Supports Windows® 2000/2003/XP/Vista/2008 Windows® 7/8 Linux, FreeBSD and MAC | |
Optional SNMP |
Power management from SNMP manager and web browser |
||
Standards |
Safety |
IEC/EN62040-1,IEC/EN62477-1 | |
EMC |
IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 |
EXTERNAL BATTERY PACK | |
Model | CNBC00396CR |
Battery Type |
VRLA (Lead acid maintenance free battery) |
Typical battery recharging time | 6~8 hours (to 90% of full capacity) |
Typical Battery Life | 3~5 years, depend on discharging cycle and ambient temperature |
System Voltage |
96Vdc |
Charging Current Max | 1.4A |
Battery Qty | 8 |
Capacity |
9Ah/12V (7Ah/12V optional |
Backup time @ 50% load | 9 minutes |
Backup time @ 100% load | 3 minutes |
Dimension | 440 x 550 x 86.5 |
Net weight(kg) | 31.5 |
Environment safety | CE |
Operating environment | 0°C~40°C |
Relative humidity | 0~95% (Non condensing) |
Noise Level | <40dB at 1 Meter |
Part Number | Description | ||
CN7003MPI-RM |
3kVA Medium Power Transformerless UPS (Internal battery) Rack Mount |
||
CN7003MPE-RM |
3kVA Medium Power Transformerless UPS (External battery) Rack Mount |
||
CNBC00396CR | 96 VDC Battery Pack |