PH 120 HFFR Insulati...

PH 120 HFFR Insulation Cable

NORDEN FireNor PH fire resistant cables are manufactured within the specific requirement of fire resistant cable standards. The fire resistant cable assures reliable circuit integrity to keep emergency evacuation systems operational even whilst the cable is burning. FireNor fire resistant cables can be used for fire alarm systems, power supply or control of equipment that needs to function during a fire such as warning, emergency lighting, evacuation and monitor systems. The place of usage is intelligent or semi-intelligent buildings where dense human population or valuable goods are found. These can be hospitals, cinemas, theatres, schools, shopping centers, airports, factories, hotels etc. FireNor products_backup have low smoke density , are halogen free and they don't emit poisonous gases. CABLE CONSTRUCTION Conductor Solid Bare CopperIEC/EN 228, BS 6360, VDE 0295, HD 383 Screen Aluminium Laminated Polyester Tape Foil Sheath HFFR EN 50290-2,BS 7655 LTS1/LTS3VDE 0207 Insulation Double Layer Insulation (HFFR),Colour: BS7671/HD308-S2/DEO2930-308 Flame Barrier Fibre Glass Tape Sheath Color Red (RAL 3000) or White Insulation Colour 2 Core: Blue/Brown Earth Wire Tinned Copper to BS 6360 Solid 0.80mm Standard Packing Mode 100 mtr / Plywood Reel500 mtr / Plywood Reel (optional) Flame Tests Insulation Integrity Smoke Density Corrosive Gases Measurement IEC 60332-3-24IEC/EN 60332-1 - 2 BS 6387 CWZCat. C fire @ 950°C - 180 min.Cat. W fire and water @ 650°C- 15 + 15 min.Cat. Z fire and mechanicalshocks @ 950°C - 15 min.EN 50200 PH120and mechanical shocks830°C fireIEC 60331 BS 7622IEC/EN 61034 -1+2 BS EN 50267IEC 60754-2 ELECTRICAL & MECHANICAL CHARACTERISTICS Properties Value 1.5 mm² 2.5 mm² Max. Conductor Resistant @ 20ºC 12.0Ω/km 7.4 Ω/km Min. Insulation Resistant @ 0ºC 5000MΩ/km Operating Voltage 300/500 V Test Voltage 2000 V Temperature Range (Fixed) -30ºC to + 90ºC Temperature Range (Fixed) -5ºC to + 60ºC Min. Bend Radius (Fixed) 8 x D Min. Bend Radius (Fixed) 15 x D PHYSICAL INFORMATION Nom. Cond.Cross-Sect. mm² Conductor Sizeno./mm Earth Wire Sizeno./mm Cable Diametermm (±5 %) Weight Kg/km 2 x 1.5 1/1.37 1/0.80 8.00 98.0 2 x 2.5 1/1.75 1/0.80 9.70 148.0


Overview Specifications Ordering Information

Overview

NORDEN FireNor PH fire resistant cables are manufactured within the specific requirement of fire resistant cable standards. The fire resistant cable assures reliable circuit integrity to keep emergency evacuation systems operational even whilst the cable is burning. FireNor fire resistant cables can be used for fire alarm systems, power supply or control of equipment that needs to function during a fire such as warning, emergency lighting, evacuation and monitor systems. The place of usage is intelligent or semi-intelligent buildings where dense human population or valuable goods are found. These can be hospitals, cinemas, theatres, schools, shopping centers, airports, factories, hotels etc. FireNor products_backup have low smoke density , are halogen free and they don't emit poisonous gases.

CABLE CONSTRUCTION

Conductor

Solid Bare Copper
IEC/EN 228, BS 6360, VDE 0295, HD 383

Screen

Aluminium Laminated Polyester Tape Foil

Sheath

HFFR EN 50290-2,
BS 7655 LTS1/LTS3
VDE 0207

Insulation

Double Layer Insulation (HFFR),
Colour: BS7671/HD308-S2/DEO2930-308

Flame Barrier

Fibre Glass Tape

Sheath Color

Red (RAL 3000) or White

Insulation Colour

2 Core: Blue/Brown

Earth Wire

Tinned Copper to BS 6360 Solid 0.80mm

Standard Packing Mode

100 mtr / Plywood Reel
500 mtr / Plywood Reel (optional)

Flame Tests Insulation Integrity Smoke Density Corrosive Gases Measurement

IEC 60332-3-24
IEC/EN 60332-1 - 2

BS 6387 CWZ
Cat. C fire @ 950°C - 180 min.
Cat. W fire and water @ 650°C
- 15 + 15 min.
Cat. Z fire and mechanical
shocks @ 950°C - 15 min.
EN 50200 PH120
and mechanical shocks
830°C fire
IEC 60331

BS 7622
IEC/EN 61034 -1+2

BS EN 50267
IEC 60754-2

ELECTRICAL & MECHANICAL CHARACTERISTICS

Properties Value
1.5 mm² 2.5 mm²

Max. Conductor Resistant @ 20ºC

12.0Ω/km

7.4 Ω/km

Min. Insulation Resistant @ 0ºC

5000MΩ/km

Operating Voltage

300/500 V

Test Voltage

2000 V

Temperature Range (Fixed)

-30ºC to + 90ºC

Temperature Range (Fixed)

-5ºC to + 60ºC

Min. Bend Radius (Fixed)

8 x D

Min. Bend Radius (Fixed)

15 x D

PHYSICAL INFORMATION

Nom. Cond.
Cross-Sect. mm²
Conductor Size
no./mm
Earth Wire Size
no./mm
Cable Diameter
mm (±5 %)
Weight Kg/km

2 x 1.5

1/1.37

1/0.80

8.00

98.0

2 x 2.5

1/1.75

1/0.80

9.70

148.0

Specifications

CABLE CONSTRUCTION

Conductor

Solid Bare Copper
IEC/EN 228, BS 6360, VDE 0295, HD 383

Screen

Aluminium Laminated Polyester Tape Foil

Sheath

HFFR EN 50290-2,
BS 7655 LTS1/LTS3
VDE 0207

Insulation

Double Layer Insulation (HFFR),
Colour: BS7671/HD308-S2/DEO2930-308

Flame Barrier

Fibre Glass Tape

Sheath Color

Red (RAL 3000) or White

Insulation Colour

2 Core: Blue/Brown

Earth Wire

Tinned Copper to BS 6360 Solid 0.80mm

Standard Packing Mode

100 mtr / Plywood Reel
500 mtr / Plywood Reel (optional)

Flame Tests Insulation Integrity Smoke Density Corrosive Gases Measurement

IEC 60332-3-24
IEC/EN 60332-1 - 2

BS 6387 CWZ
Cat. C fire @ 950°C - 180 min.
Cat. W fire and water @ 650°C
- 15 + 15 min.
Cat. Z fire and mechanical
shocks @ 950°C - 15 min.
EN 50200 PH120
and mechanical shocks
830°C fire
IEC 60331

BS 7622
IEC/EN 61034 -1+2

BS EN 50267
IEC 60754-2

ELECTRICAL & MECHANICAL CHARACTERISTICS

Properties Value
1.5 mm² 2.5 mm²

Max. Conductor Resistant @ 20ºC

12.0Ω/km

7.4 Ω/km

Min. Insulation Resistant @ 0ºC

5000MΩ/km

Operating Voltage

300/500 V

Test Voltage

2000 V

Temperature Range (Fixed)

-30ºC to + 90ºC

Temperature Range (Fixed)

-5ºC to + 60ºC

Min. Bend Radius (Fixed)

8 x D

Min. Bend Radius (Fixed)

15 x D

PHYSICAL INFORMATION

Nom. Cond.
Cross-Sect. mm²
Conductor Size
no./mm
Earth Wire Size
no./mm
Cable Diameter
mm (±5 %)
Weight Kg/km

2 x 1.5

1/1.37

1/0.80

8.00

98.0

2 x 2.5

1/1.75

1/0.80

9.70

148.0

Ordering Information

Part Number Description

54-1502X

FireNor FE 180 PH120 Fire Resistant Cable 2C x 1.5 mm²

54-2502X