PH 30 Improved Fire...

PH 30 Improved Fire Resistant Cable

NORDEN FireNor PH30 Improved fire resistant cables are manufactured within the specific requirement of fire resistant cable standards. The fire resistant cable assures reliable circuit integrity to keep emergency evacuation systems operational even whilst the cable is burning


Overview Specifications Ordering Information

Overview

NORDEN FireNor PH30 Improved fire resistant cables are manufactured within the specific requirement of fire resistant cable standards. The fire resistant cable assures reliable circuit integrity to keep emergency evacuation systems operational even whilst the cable is burning

Specifications

CABLE CONSTRUCTION

Conductor

Bare Copper

Screen

Aluminium Tape
(100 % Coverage)

Sheath

LSZH, Halogen Free Flame Retardant, LTS3

Insulation

Fire Resistant Silicon Rubber - E12

Binding Tape

Mica Tape

Sheath Color

Red ( RAL 3000) or White

Insulation Colour

2 Core: Blue/Brown
3 Core: Blue/Brown/Black
4 Core: Blue/Brown/Black/Grey

Earth Wire

Tinned Copper to BS 6360 Solid 0.80mm

Standard Packing Mode

100 mtr / Plywood Reel
500 mtr / Plywood Reel (optional)

Flame Tests Insulation Integrity Smoke Density Corrosive Gases Measurement LPCB Certified Standards

BS 4066 part 1 & 3
EN 50266-2-4
IEC 60332-3-24
IEC/EN 60332-1

IEC 60331
BS 6387 CWZ
EN 50200 PH30
EN 50200 Annex E(30 min)

BS 7622
IEC/EN 61034
 

BS EN 50267-2-2
IEC 60754-2

BS 7629-1:2008
BS 6387:2013 (Category CWZ)
EN 50200:2006 (Class PH30)
EN50200:2006 Annex E (30 min)
BS 5839-1:2013 (Clause 26.2d
standard

ELECTRICAL & MECHANICAL CHARACTERISTICS

Properties Value
1.0 mm² 1.5 mm² 2.5 mm²

Max. Conductor Resistant @ 20ºC

18.0 ?/km

12.0 ?/km

7.4 ?/km

Min. Insulation Resistant @ 0ºC

200 M?/km

Operating Voltage

300/500 V

Test Voltage

2000 V

Temperature Range (Fixed)

-30ºC to + 90ºC

Temperature Range (Flexing)

-5ºC to + 60ºC

Min. Bend Radius (Fixed)

8 x D

Min. Bend Radius (Flexing)

15 x D

PHYSICAL INFORMATION

Nom. Cond.
Cross-Sect. mm²
Conductor Size
no./mm
Earth Wire Size
no./mm
Cable Diameter
mm (±5 %)
Weight Kg/km

2 x 1.0

1/1.12

1/0.80

5.80

51.0

2 x 1.5

1/1.37

1/0.80

6.65

70.0

2 x 2.5

1/1.75

1/0.80

7.80

100.0

3 x 1.0

1/1.12

1/0.80

6.00

65.0

3 x 1.5

1/1.37

1/0.80

6.75

90.0

3 x 2.5

1/1.75

1/0.80

8.25

135.0

4 x 1.0

1/1.12

1/0.80

6.60

81.0

4 x 1.5

1/1.37

1/0.80

7.60

110.0

4 x 2.5

1/1.75

1/0.80

9.10

165.0

Ordering Information

Part Number Description

62-1002X

PH30 Improved Fire Resistant Cable, 2C x 1.0 mm²

62-1502X

PH30 Improved Fire Resistant Cable, 2C x 1.5 mm²

62-2502X

PH30 Improved Fire Resistant Cable, 2C x 2.5 mm²

62-1003X

PH30 Improved Fire Resistant Cable, 3C x 1.0 mm²

62-1503X

PH30 Improved Fire Resistant Cable, 3C x 1.5 mm²

62-2503X

PH30 Improved Fire Resistant Cable, 3C x 2.5 mm²

62-1004X

PH30 Improved Fire Resistant Cable, 4C x 1.0 mm²

62-1504X

PH30 Improved Fire Resistant Cable, 4C x 1.5 mm²

62-2504X

PH30 Improved Fire Resistant Cable, 4C x 2.5 mm²

X > RD:Red WH:White OR:Orange