Norden single-core single insulated XL-HFFR fire-resistant power cable can be used in cable wiring systems that require improved fire performance and circuit integrity. These cables are mainly used in installations where a fire situation may pose a major hazard (trunking and conduits). The Fire-resistant cable assures reliable circuit integrity to keep emergency evacuation systems operational even whilst the cable is burning.
Overview Specifications Ordering Information
ConductorStranded Annealed Copper (IEC/BS/EN 60228 - Class 2) |
Fire BarrierMica Tape |
InsulationXL-HFFR |
Properties | Value | |
1.5 mm² - 10 mm² | 16 mm² - 300 mm² | |
Operating Voltage | 450/750V | |
Test Voltage | 2500 V | 3500 V |
Insulation Resistance | min. 4000 MΩ.km | |
Operation Temperature | 30°C to + 90°C | |
Min. Bending Radius | 8 x D |
Nom. Cond. Cross-Sect. mm² |
Insulation Thickness(mm) | Cable Diameter mm (±5 %) |
Max. Conductor Resistance[Ω/km] | Copper Weight [kg/km] | Cable Weight [kg/km] |
1x1.5 mm² | 0.7 | 3.90 | 12.1 | 13.4 | 27.2 |
1x2.5 mm² | 0.8 | 4.50 | 7.14 | 21.5 | 39.4 |
1x4 mm² | 0.8 | 5.00 | 4.61 | 34.4 | 55.1 |
1x6 mm² | 0.8 | 5.60 | 3.08 | 51.6 | 75.5 |
1x10 mm² | 1.0 | 6.70 | 1.83 | 92.8 | 126.4 |
1x16 mm² | 1.0 | 7.60 | 1.15 | 140.0 | 179.8 |
1x25 mm² | 1.2 | 9.30 | 0.727 | 220.6 | 281.8 |
1x35 mm² | 1.2 | 10.30 | 0.524 | 300.0 | 369.3 |
1x50 mm² | 1.4 | 11.80 | 0.387 | 407.0 | 505.5 |
1x70 mm² | 1.4 | 13.90 | 0.268 | 605.5 | 706.0 |
1x95 mm² | 1.6 | 15.50 | 0.193 | 856.2 | 980.9 |
1x120 mm² | 1.6 | 18.10 | 0.153 | 1056.3 | 1204.1 |
1x150 mm² | 1.8 | 19.00 | 0.124 | 131.8 | 1486.8 |
1x185 mm² | 2.0 | 21.30 | 0.0991 | 1572.0 | 1856.6 |
1x240 mm² | 2.2 | 24.40 | 0.0754 | 2061.0 | 2323.8 |
1x300 mm² | 2.4 | 26.80 | 0.0601 | 2600.0 | 3212.4 |
Part Number | Description |
6G-1501X | 1 Core 1.5 Sq.mm Single Core -Single insulated Fire-Resistant Power Cable XL-HFFR |
6G-2501X | 1 Core 2.5 Sq.mm Single Core -Single insulated Fire-Resistant Power Cable XL-HFFR |
6G-4001X | 1 Core 4 Sq.mm Single Core -Single insulated Fire-Resistant Power Cable XL-HFFR |
6G-6001X | 1 Core 6 Sq.mm Single Core -Single insulated Fire-Resistant Power Cable XL-HFFR |
6G-1001X | 1 Core 10 Sq.mm Single Core -Single insulated Fire-Resistant Power Cable XL-HFFR |
6G-1601X | 1 Core 16 Sq.mm Single Core -Single insulated Fire-Resistant Power Cable XL-HFFR |
6G-2001X | 1 Core 25 Sq.mm Single Core -Single insulated Fire-Resistant Power Cable XL-HFFR |
6G-3501X | 1 Core 35 Sq.mm Single Core -Single insulated Fire-Resistant Power Cable XL-HFFR |
6G-5001X | 1 Core 50 Sq.mm Single Core -Single insulated Fire-Resistant Power Cable XL-HFFR |
6G-7001X | 1 Core 70 Sq.mm Single Core -Single insulated Fire-Resistant Power Cable XL-HFFR |
6G-9501X | 1 Core 95 Sq.mm Single Core -Single insulated Fire-Resistant Power Cable XL-HFFR |
6G-0A01X | 1 Core 120 Sq.mm Single Core -Single insulated Fire-Resistant Power Cable XL-HFFR |
6G-0B01X | 1 Core 150 Sq.mm Single Core -Single insulated Fire-Resistant Power Cable XL-HFFR |
6G-0C01X | 1 Core 185 Sq.mm Single Core -Single insulated Fire-Resistant Power Cable XL-HFFR |
6G-0D01X | 1 Core 240 Sq.mm Single Core -Single insulated Fire-Resistant Power Cable XL-HFFR |
6G-0E01X | 1 Core 300 Sq.mm Single Core -Single insulated Fire-Resistant Power Cable XL-HFFR |
X > RD:Red OR:Orange BL:Blue BK:Black