SINGLE CORE -SINGLE...

SINGLE CORE -SINGLE INSULATED XL-HFFR FIRE RESISTANT POWER CABLE

Norden single-core single insulated XL-HFFR fire-resistant power cable can be used in cable wiring systems that require improved fire performance and circuit integrity. These cables are mainly used in installations where a fire situation may pose a major hazard (trunking and conduits). The Fire-resistant cable assures reliable circuit integrity to keep emergency evacuation systems operational even whilst the cable is burning. 


Overview Specifications Ordering Information

Overview

Norden single-core single insulated XL-HFFR fire-resistant power cable can be used in cable wiring systems that require improved fire performance and circuit integrity. These cables are mainly used in installations where a fire situation may pose a major hazard (trunking and conduits). The Fire-resistant cable assures reliable circuit integrity to keep emergency evacuation systems operational even whilst the cable is burning. 

Specifications

CABLE CONSTRUCTION

Conductor

Stranded Annealed Copper

(IEC/BS/EN 60228 - Class 2)

Fire Barrier

Mica Tape

Insulation      

XL-HFFR

 

STANDARD COMPLIANCE:

  • BS EN 50363-5
  • EC 60332-1-2
  • IEC 60331-21, EN 50200 PH120, BS 6387 CWZ
  • IEC 61034-1/2
  • IEC 60754-1/2 

ELECTRICAL & MECHANICAL CHARACTERISTICS

Properties Value
1.5 mm² - 10 mm² 16 mm² - 300 mm²
Operating Voltage  450/750V  
Test Voltage 2500 V 3500 V
Insulation Resistance min. 4000 MΩ.km
Operation Temperature 30°C to + 90°C
Min. Bending Radius 8 x D

PHYSICAL INFORMATION

Nom. Cond.
Cross-Sect. mm²
Insulation Thickness(mm)  Cable Diameter
mm (±5 %)
Max. Conductor Resistance[Ω/km]  Copper Weight [kg/km]  Cable Weight [kg/km] 
1x1.5 mm² 0.7 3.90 12.1 13.4 27.2
1x2.5 mm² 0.8 4.50 7.14 21.5 39.4
1x4 mm²  0.8 5.00 4.61 34.4 55.1
1x6 mm² 0.8 5.60 3.08  51.6 75.5 
1x10 mm² 1.0 6.70 1.83 92.8 126.4
1x16 mm²  1.0 7.60 1.15 140.0 179.8
1x25 mm²  1.2  9.30 0.727 220.6 281.8
1x35 mm² 1.2  10.30 0.524 300.0  369.3
1x50 mm² 1.4 11.80 0.387  407.0 505.5
1x70 mm²  1.4 13.90 0.268 605.5 706.0
1x95 mm²  1.6  15.50 0.193 856.2 980.9 
1x120 mm²  1.6  18.10 0.153  1056.3 1204.1 
1x150 mm² 1.8 19.00 0.124 131.8 1486.8
1x185 mm² 2.0 21.30 0.0991 1572.0 1856.6
1x240 mm²  2.2  24.40 0.0754 2061.0 2323.8
1x300 mm² 2.4 26.80 0.0601  2600.0  3212.4

Ordering Information

Part Number Description
6G-1501X 1 Core 1.5 Sq.mm Single Core -Single insulated Fire-Resistant Power Cable XL-HFFR
6G-2501X 1 Core 2.5 Sq.mm Single Core -Single insulated Fire-Resistant Power Cable XL-HFFR 
6G-4001X 1 Core 4 Sq.mm Single Core -Single insulated Fire-Resistant Power Cable XL-HFFR
6G-6001X  1 Core 6 Sq.mm Single Core -Single insulated Fire-Resistant Power Cable XL-HFFR 
6G-1001X 1 Core 10 Sq.mm Single Core -Single insulated Fire-Resistant Power Cable XL-HFFR
6G-1601X 1 Core 16 Sq.mm Single Core -Single insulated Fire-Resistant Power Cable XL-HFFR
6G-2001X 1 Core 25 Sq.mm Single Core -Single insulated Fire-Resistant Power Cable XL-HFFR
6G-3501X  1 Core 35 Sq.mm Single Core -Single insulated Fire-Resistant Power Cable XL-HFFR
6G-5001X 1 Core 50 Sq.mm Single Core -Single insulated Fire-Resistant Power Cable XL-HFFR
6G-7001X 1 Core 70 Sq.mm Single Core -Single insulated Fire-Resistant Power Cable XL-HFFR
6G-9501X  1 Core 95 Sq.mm Single Core -Single insulated Fire-Resistant Power Cable XL-HFFR
6G-0A01X 1 Core 120 Sq.mm Single Core -Single insulated Fire-Resistant Power Cable XL-HFFR
6G-0B01X 1 Core 150 Sq.mm Single Core -Single insulated Fire-Resistant Power Cable XL-HFFR
6G-0C01X 1 Core 185 Sq.mm Single Core -Single insulated Fire-Resistant Power Cable XL-HFFR
6G-0D01X 1 Core 240 Sq.mm Single Core -Single insulated Fire-Resistant Power Cable XL-HFFR 
6G-0E01X 1 Core 300 Sq.mm Single Core -Single insulated Fire-Resistant Power Cable XL-HFFR

X > RD:Red OR:Orange BL:Blue BK:Black