MAXPOWER PRO is a small to medium power transformer-less UPS of CellNor. This UPS has a high output power factor at 0.9PF and a wide input voltage range 110~286Vac. The CN6006MPI, CN6006MPE model support economic (ECO) operation mode.
Overview Specifications Ordering Information
GENERAL FEATURES
N+X parallel redundancy, support maximum 4 unit in parallel
Online double conversion with full digital control
Selectable output voltage:220/230/240VacOnline double conversion with full digital control
Wide input voltage range:110~286Vac
Maximum charging current up to 10A
Optimization battery group, the quantity of battery: 16/18/20Pcs (Settable)
ECO mode operation for energy saving Multiple communication interface:RS232
(USB/Dry contact/SNMP card optional)Maximum charging current up to 10A
Self-testing when UPS start-up
Generator compatible
Model | CN6006MPI, CN6006MPE | ||
Capacity |
VA |
6000 |
|
Watts |
5400 |
||
Input |
Normal Voltage |
220/230/240Vac(L+N+PE) | |
Operating Voltage Range |
110~286Vac |
||
Operating Frequency Range |
40~70Hz (50/60Hz Auto-Sensing) |
||
Power Factor |
≥0.99 |
||
Bypass voltage range |
Max.voltage:230~264Vac Min.voltage:176~220Vac |
||
ECO range |
Same as the bypass |
||
Harmonic distortion (THDi) |
≤5%(100% linear load) |
||
Generator input |
Support |
||
Output |
Output voltage |
220/230/240Vac | |
Power factor |
0.9 |
||
Voltage Regulation |
±1% |
||
Frequency |
Line mode |
±1%/±2%/±4%/±5%/±10% of the rated frequency(optional) | |
Bat. mode |
50/60(±0.1)Hz |
||
Crest Factor |
3:1 |
||
Harmonic Distortion (THDv) |
≤2% with linear load, ≤5% with non-linear load |
||
Efficiency |
>93.5% |
||
Battery |
Battery voltage |
192/216/240Vdc (Adjustable) with Neutral, (Standard unit 240Vdc) | |
Capacity (Standard unit) |
9Ah/12V (7Ah/12V optional) |
||
Typical recharging time |
6~8 hours (to 90% of full capacity) |
||
Charging current |
1A(Standard unit); Long run unit Max.current 10A(charging current can be set according to battery capacity installed) |
||
System |
Transfer time |
Mains to battery:0ms; Mains to bypass:0ms | |
Overload |
Line mode |
Load≤110%: last 60min, ≤125%: last 10min, ≤150%: last 1min, >150% turn to bypass mode immediately | |
Bypass mode |
40A(Breaker) |
||
Short circuit |
Hold whole system |
||
Overheat |
Line mode: Turn to bypass; Backup mode: shut down UPS immediately |
||
Battery low |
Alarm and switch off |
||
Self-diagnostics |
Upon power on and software control |
||
Battery |
Advanced battery management |
||
Audible & Visual alarms |
Line failure, Battery under voltage, Overload, System fault |
||
LED & LCD display |
Line mode, Bat. mode, Eco mode, Bypass mode, Battery under voltage, Overload & UPS Fault |
||
LCD display |
Input voltage, Input frequency, Output voltage, Output frequency, Load percentage, Battery voltage, Inner temperature & Remaining battery backup time |
||
Communication interface |
RS232, USB,SNMP card(optional), Parallel card(optional), Relay card (optional) |
||
Environment |
Operating temperature |
0~40°C | |
Storage temperature |
-25~55°C |
||
Humidity range |
0~95% (Non-condensing) |
||
Altitude |
<1500m |
||
Noise level |
<55dB |
||
Standards |
Safety |
IEC/EN62040-1,IEC/EN62477-1 | |
EMC |
IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 |
||
Physical |
Dimension |
I:191 x 460 x 720 E:191 x 460 x 337 | |
Net Weight (kg) |
69 12 |
MODEL | CNBC06120CR | ||
BATTERY SYSTEM | |||
Battery type |
VRLA (Lead acid maintenance free battery) |
||
Typical battery recharging time |
6~8 hours (to 90% of full capacity) |
||
Typical battery life | 3~5 years, depend on discharging cycle and ambient temperature | ||
System voltage | ±120Vdc | ||
Battery quantity | 2*±10 Pcs | ||
Capacity | 7Ah/9Ah (12V) | ||
Backup time @ 50% load | 43 minutes | ||
Backup time @ 100% load | 15 minutes | ||
PHYSICAL | |||
Dimension W x D x H (mm) | 250 x 597 x 616 | ||
Net weight (kg) | 122/134 | ||
ENVIRONMENT | |||
Safety | CE | ||
Operating environment | 0°C~40°C | ||
Relative humidity | 0~95% (Non condensing) | ||
Noise level | <40dB at 1 Meter |
Part Number | Description | ||
CN6006MPI |
6kVA Medium Power Transformerless UPS (internal battery) |
||
CN6006MPE |
6kVA Medium Power Transformerless UPS (external battery) | ||
CNBN06120CT | 120 VDC Battery Pack |