NORDEN XLPE Insulated PH 30 fire resistant cables are manufactured within the specific requirement of fire resistant cable standards. The fire resistant cable assures reliable circuit integrity to keep emergency evacuation systems operational even whilst the cable is burning.
Overview Specifications Ordering Information
ConductorStranded annealed copper wire |
Outer SheathHalogen Free Flame |
Ref. StandardsIEC 60502 ( Adapted) |
InsulationMica Tape+ XLPE ( EN 50290-2) |
Lay-UpCore stranded together with talk powder |
Length Tolerance±5% |
Core ColorsWhite cores with numbers |
|
|
Flame Tests | Insulation Integrity | Smoke Density | Corrosive Gases Measurement |
IEC /EN 60332-1 |
IEC 60331(3hrs. fire test @750°C) |
EN/IEC 61034 |
IEC 60754-2 |
Properties | Value | ||
Cross Section (mm²) | 1.0 | 1.50 | 2.50 |
Conductor (Cu) |
7*0.43 mm | 7*0.52 mm | 7*0.66 mm |
Operating Voltage |
600/1000 V |
||
Test Voltage (1 min) |
3500 V |
||
Conductor Resistance(max. Ω/km) |
According to IEC 60228, HD383, BS6360 |
||
Insulation Resistance (min. MΩ.km) |
5000 |
||
Temperature Range |
fixed -40°C to +90°C, during installation -5°C to +55°C |
||
Min. Bending Radius (fixed) |
10 x Cable diameter |
||
Oxygen Index |
Min.34% |
||
Oil Resistance ( IEC 60811) |
ASTM No 2 oil 70°C 4 hours |
Nom. Cond. Cross-Sect. (mm²) |
Conductor Size no./mm |
Cable Diameter mm (±5 %) |
Weight Kg/km | Max. Conductor resistance @ 20°C (Ω/km) |
2x1.0 |
7/0.43 |
10.9 |
140 |
18.1 |
2x1.5 |
7/0.52 |
11.3 |
157 |
12.1 |
2x2.5 | 7/0.66 | 12.1 | 190 | 7.41 |
60-1011X | 1 Pair 1.0 Sq.mm Mica Tape XLPE Insulated PH30 Fire Resistant Cable 500V |
60-1511X | 1 Pair 1.5 Sq.mm Mica Tape XLPE Insulated PH30 Fire Resistant Cable 500V |
60-2511X | 1 Pair 2.5 Sq.mm Mica Tape XLPE Insulated PH30 Fire Resistant Cable 500V |
X:BK:Black BL:Blue OR:Orange